Push until the door opens all the way.
Fire rated door opening force.
5 0 pounds 22 2 n maximum.
The force for pushing or pulling open doors other than fire doors shall be as follows.
This standard regulates the installation and maintenance of assemblies and devices used to protect openings in walls floors and ceilings against the spread of fire and smoke within into or out of buildings.
I got an email today about a fire rated door that would not reliably close with the closer adjusted to provide 5 pounds of opening force.
Life safety code the international building code ibc and the international fire code ifc.
It is an offence to prop open or otherwise interfere with the automatic closing action of a fire door.
The force for pushing or pulling open interior swinging egress doors other than fire doors shall not exceed 5 pounds.
5 0 pounds 22 2 n maximum 2.
Standard for fire doors and other opening protectives nfpa 101.
Fire doors must only be fitted with door hardware fire rated in accordance with as1905 1.
Sliding or folding door.
Measure door opening force and closing speed.
This is clearly stated in the accessibility standards.
A 1 1 see annex k for general information about fire doors.
Fire doors must also be fitted with a fire rated automatic non.
Door opening force fire doors shall have a minimum opening force allowable by the appropriate administrative authority.
Latching and locking doors that are hand activated and which are in a path of travel shall be operable with a single effort by lever type hardware by panic bars push pull activating bars or other hardware designed to provide passage.
For other swinging doors as well as sliding and folding doors the door latch shall release when subjected to a i5 pound force.
The force for pushing or pulling open a door or gate.
The door shall be set in motion when subjected to a 30 pound force.
Fire doors shall have the minimum opening force allowable by the appropriate administrative authority.
Fire rated door assemblies must meet the requirements of the applicable building or life safety code such as the national fire protection association nfpa 80.
I did a post on opening force for accessibility a while back but it s important to note that fire rated doors are not required to open with 5 pounds of force.
The readout on the gauge shows you the force required to open the door.
1 1 1 with the exception of fabric fire safety curtain assemblies this standard addresses assemblies that have.
To do this first unlatch the door and then press the gauge against the door.
2 hand activated door opening hardware shall be centered between 30 inches and 44 inches above the floor.
Fire door locks must be self latching and are not permitted to have a hold open feature.
Spring hinges door spring hinges shall be adjusted so that from the open position of 70 degrees the door shall move to the closed position in 1 5 seconds minimum.